GIS 123 kV
Main characteristics
- Possibility of installation in very limited space.
- High degree of safety during operation.
- Auto-blow type switch.
- Low electrical damage.
- No impact on the environment.
- Minimal gas leakage.
- Simple and quick installation on site.
- Minimal maintenance.
Description
The complete gas-insulated switchgear type K8D.6-N is designed as a three-pole switchgear in a protective casing made of aluminum alloy using standard mounting modules allowing for various configurations.
The main cell of the K8D.6-N switchgear is a vertically located circuit breaker with an integrated current transformer, which carries all other components of the cell.
The standard cable compartment of the switchgear is installed, tested and delivered to the site as a complete transport unit filled with SF6 gas.
Drive mechanism
The drive mechanism with a spring electric drive is characterized by reliability, simple and quick installation, as well as decent contact closing/opening time. The drive is housed in a drive cabinet made of aluminum, which ensures lighter weight of the switch and better anti-corrosion properties. In addition to standard accessories that can be customized to suit customer needs, what makes the switch unique is the presence of a test connector used for monitoring or diagnostics during operation. Information on additional monitoring equipment is provided upon customer request.
Specifications | 123 kV | |
Rated voltage | kV | 123 |
Rated lightning impulse withstand voltage(1.2/50µs) | kV | 550 |
Rated power frequency withstand voltage (1 min) | kV | 230 |
Rated frequency | Hz | 50/60 |
Rated normal current | A | ...3150 |
Rated breaking current | kA | ...40 |
Rated thermal current | kA | ...40 |
(1/3s) | ||
Rated electrodynamic withstand current | kA | ...104 |
Nominal cycle time | 0-0.3s-B0-3min-B0 or B0-15s-B0 | |
Own shutdown time | ms | 25 |
Own switching time | ms | 60 |
Electrical and mechanical wear resistance class | E2 M2 | |
Operating voltage | In DC | 110/125/220 |
Motor voltage | V AC/B DC | 110/125/220 |
Operating temperature range | °C | -5...+50 |
Applicable standards | IEC 62271-1, IEC 62271-203 |