High-voltage SF6 circuit breaker for outdoor installation type 8 E-1 up to 145 kV

HIGH VOLTAGE SF6 GAS BREAKER FOR EXTERNAL INSTALLATION TYPE 8 E-1 UP TO 145 KV INSTALLATIONS TYPE 8 E-1 UP TO 145 KV

Based on a 60-year tradition of successful production and operation of high-voltage circuit breakers, the KONČAR group of companies has developed and tested SF6 circuit breakers of type 8E-1.
Unlike the previous generation of SF6 circuit breakers, the 8E-1 is characterized by additional optimization of the arc extinguishing device, a new electric drive mechanism and a very low overall weight. At customers' request, the 8E-1 switch can be supplied with one or three poles, i.e. with one or three drive mechanisms (one per pole).

Pole column

The pole column consists of an arc suppressor, silicon or porcelain support insulators, and a mechanical transmission composition. The poles are assembled, configured and tested at the factory, pre-filled with SF6 gas, and supplied in a minimum number of transport kits, which reduces assembly time at the station. A mathematical model of electric arc extinguishing was developed to meet the requirements for the creation and optimization of an arc extinguishing device operating on proven auto-compression technology.

itself autocompression technology.
Auto-compression arc extinguishing circuit diagram

Drive mechanism

The drive mechanism with a spring electric drive, characterized by reliability, quick and easy installation at the station and decent contact closing/opening time, is housed in a drive cabinet made of aluminum, which ensures lower weight of the circuit breaker and anti-corrosion properties. In addition to the standard accessories that can be customized to suit the customer's needs, what makes the switch unique is the presence of a test connector used for monitoring or diagnostic purposes during operation.
Information on additional monitoring equipment is provided upon customer request. available upon customer's request.
Diagram of a spring electric drive of a switch in four characteristic positions (blue – turning on, red – opening spring): 

a) both springs are unloaded;
b) the closing spring is loaded, the opening spring is unloaded;
c) the closing spring is unloaded, the opening spring is loaded;
d) both springs are loaded.

 

 

Technical specifications Unit 123-145 kV
Rated voltage kV 123 145
Rated lightning impulse withstand voltage (1.2/50s°µ) kV 550 650
Rated frequency withstand voltage kV 230 275
Rated frequency Hz 50/60
Rated normal current A 3150/4000
Rated breaking current kA 40(50)
Rated thermal current kA 40(50)
Rated electrodynamic withstand current kA 100(125)
Normalized switching cycle   0-0.3s-B0-3min-B0 or ​​B0-15s-B0
Own shutdown time ms 25
Own switching time ms 60
Switching and mechanical wear resistance class   E2, M2
Operating voltage In DC 110/125/220
Motor voltage V DC/V AC 110/125/220
Operating temperature range (-45)-30...+40
Applicable Standards   IEC 62271-100, IEC 62271-1

Dimensions of three-pole switch 8E1 – III

Rated voltage kV 123 145
Interpolar distance (p) mm 1750 1750
Height (h1) mm 3038 3288
Length (b1) mm 4000 4000

 

Dimensions of a three-pole switch