Transformer high-voltage bushings with a voltage of 220 kV with RIP insulation are available with a porcelain insulator (ETFt series) and with a polymer insulator (SETFt series) in accordance with the international standard IEC 60137.
RIP-insulated transformer bushings ETFt/SETFt series | |||||
Technical specifications | U measurement | 245-A1 | 245-B1 | 245-A2 | 245-B2 |
Highest operating voltage, Um | kV | 245 | 245 | 245 | 245 |
Highest operating phase voltage | kV | 142 | 142 | 142 | 142 |
Partial discharge level | pCL | < 5 | < 5 | < 5 | < 5 |
Power frequency test voltage 50 Hz, 1 min | kV | 505 | 505 | 505 | 505 |
Full wave lightning impulse test voltage 1.2/50 µs | kV | 1050 | 1050 | 1050 | 1050 |
Switching impulse test voltage 250/2500 µs | kV | 750 | 750 | 850 | 850 |
Typical test voltages | |||||
Full wave lightning impulse test voltage 1.2/50 µs: negative polarity | kV | 1155 | 1155 | 1155 | 1155 |
Test voltage of lightning impulse of sheared wave: negative polarity | kV | 1271 | 1271 | 1271 | 1271 |
Switching pulse test voltage 250/2500 µs in dry condition: negative polarity | kV | 825 | 825 | 935 | 935 |
Maximum operating current: continuous cable connection, Imax | A | 800 | 1250 | 800 | 1250 |
Maximum operating current: split current-carrying core, Imax | A | 1250 | 2000 | 1250 | 2000 |
Minimum arc path length, SW | mm | 2432 | 2434 | 2866 | 2866 |
Creepage distance, min. | mm | 8753 | 8755 | 10348 | 10348 |
Leak rate | l/s | 3.6 | 3.6 | 3.6 | 3.6 |
Test cantilever load | N | 4000 | 5000 | 4000 | 5000 |
Specific creepage distance | mm/kV | 35.7 | 35.7 | 42.2 | 42.2 |
Dimensions | |||||
D1 | mm | 190 | 210 | 190 | 210 |
D2 | mm | 120 | 140 | 120 | 140 |
D3 | mm | 290 | 350 | 290 | 350 |
D4 | mm | 335 | 400 | 335 | 400 |
D5 | mm | 200 | 290 | 200 | 290 |
D6 | mm | 318 | 368 | 318 | 368 |
L5 | mm | 90 | 90 | 90 | 90 |
d1 | mm | 50 | 69 | 50 | 69 |
d2 | mm | 65 | 85 | 65 | 85 |
l1 | mm | 50 | 50 | 50 | 50 |
s | mm | 20 | 20 | 20 | 20 |
i | mm | 20 | 20 | 20 | 20 |
z | 12 | 12 | 12 | 12 | |
a | ° | thirty | thirty | thirty | thirty |
Contact terminal dimensions d3 x L4 | mm | mm ≤ 1250 A = Ø 30 x 90; ≤ 1600 A = Ø 42 x 135; ≤ 2500 A = Ø 48 x 135 | |||
Size for TT installation | |||||
E | mm | 0 | 0 | 0 | 0 |
L1 | mm | 620 | 620 | 620 | 620 |
L2 | mm | 2854 | 2854 | 3286 | 3286 |
L3 | mm | 185 | 185 | 185 | 185 |
Total length, L | mm | 3474 | 3474 | 3906 | 3906 |
Size for TT installation | |||||
E | mm | 300 | 300 | 300 | 300 |
L1 | mm | 920 | 920 | 920 | 920 |
Total length, L | mm | 3774 | 3774 | 4206 | 4206 |
Size for TT installation | |||||
E | mm | 600 | 600 | 600 | 600 |
L1 | mm | 1220 | 1220 | 1220 | 1220 |
Total length, L | mm | 4074 | 4074 | 4506 | 4506 |