Advantages:
- No partial discharges
- Solid RIP insulated design
- Porcelain or polymer insulator
- Expanded range of bushings with rated voltage: 24-245 kV
- Maintenance free
- Fast delivery time
- Possibility to use at ambient temperature – 60°C
Main technical characteristics
STARIP®+/STARIP®-Si+ | 24 | 36 | 52 | 73 | 126 | 145 | 172 | 245 | ||
Highest operating voltage 50/60 Hz | kV | 24 | 36 | 52 | 72.5 | 126 | 145 | 172 | 245 | |
Partial discharge level | pCL | < 5 | < 5 | < 5 | < 5 | < 5 | < 5 | < 5 | < 5 | |
Test voltage: 50 Hz;1 min. dry | kV | 55 | 77 | 105 | 155 | 255 | 305 | 355 | 505 | |
Lightning impulse test voltage: 1.2/50 µs | kV | 125 | 170 | 250 | 325 | 550 | 650 | 750 | 1050 | |
Switching test voltage pulse: 250/2500 µs | kV | – | – | – | – | – | – | – | 850 | |
Maximum rated current: Imax/450 mm 2 | A | 800 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | |
Maximum rated current (removable core): Imax | A | 1600 | 1600 | 1600 | 1600 | 1600 | 1600 | 1250 | 1250 | |
Maximum rated current fixed core): Imax | A | 2500 | 2500 | 2500 | 2500 | 2000 | 2000 | 2000 | 1600 | |
Minimum arc path length | mm | S.W. | 380 | 380 | 661 | 661 | 1138 | 1301 | 1451 | 2770 |
Creepage distance | mm | 1120 | 1120 | 2250 | 2250 | 3900 | 4500 | 5270 | 9300 | |
Specific creepage distance | mm/kV | 46.7 | 31.1 | 43.3 | 31.0 | 31.7 | 31.0 | 31.0 | 38.0 |
Standard: IEC 60137-2017, possible adaptation to DSTU EN 60137:2016
CATALOG Transformer high-voltage bushings with RIP insulation STARIP®+/STARIP®-Si+ series