Motor drives HYUNDAI

Motor drive (MZ) 

  • The drive is mounted vertically on the outside of the transformer tank (bell or other type) and is convenient for control and maintenance.
  • The developed motor drives meet the requirements for operation in all climatic conditions
  • Motor drives meet the requirements of IEC 60214-1-2003
  • Motor drives type MZ-4.4 meet the requirements of the ANS standard

 meet the requirements of the ANS standard

 

MOTOR DRIVE MZ 4.4                     MZ 4.1
Rated power of electric motor, kW 0.75 /1.1(0.9/1.3 at 60 Hz) 0.75/1.1(0.9/1.3 at 60 Hz)
Rated frequency, Hz 50 / 60 50 / 60
Supply voltage, V 3 AC 400 / 230 3 AC 400 / 230
Synchronous speed, min-1 1500 (1800 at 60 Hz) 1500 (1800 at 60 Hz)
Number of crank revolutions for one shift, revs 33 33
Rated torque of the output shaft, Nm 17 / 24 17 / 24
Switching duration, s 4.5 4.5
Maximum number of working positions 38 38
Operating circuit supply voltage, V AC 230 AC 230
Insulation level, kV 2.5 2.5
Heater power, W 250 2x150
Degree of protection IP 54 IP 54
Weight, kg 104 80

Motor drives are also available in special designs according to customer requirements, e.g.:

  • with degree of protection IP 65
  • with output shaft speed for one shift: 0.5; 1; 6; 16.5
  • number of steps - up to 125